Siemens 6MD85 Manual page 81

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Data Substitute Values
Depending on the data type, different data substitute values must be used.
Data Type
ACD, ACT
BAC, APC
BCR
CMV
DPC, DPS
INC
INS
ISC, BSC
SPC, SPS
MV
For controllable types, the following substitute values apply in addition to the settable state values or meas-
ured values:
ctlNum
stSeld
origin.orIdent =
origin.orCat
Previous Quality Processing/Affected by the User for Received GOOSE Values
In the Information Routing editor, you can influence the data value and quality of all data types. The
following figure shows the possible influence using the example of a DPC data type.
In the DIGSI 5 project tree, double-click Information Routing.
Select the desired signal in the External Signals group.
Open the Properties window and select the Processing Quality Attributes sheet.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Possible Data Substitute Values
general
mxVal
actVal
mag, ang
stVal
stVal
stVal
valWTr.posVal
valWTr.transInd
stVal
mag
=
0
=
False
Substituted by quality processing
=
AUTOMATIC_BAY
0 (False), 1 (True)
(The directional information is always manually updated with
unknown .
PhsA, phsB, phsC, and neut are manually updated with the same
value just like how the general value is set.)
Floating-point range and range of values according to IEEE 754
(single precision)
–2
63
to 2
63
– 1
Floating-point range and range of values according to IEEE 754
(single precision)
0, 1, 2, 3 (intermediate-state, off, on, bad-state)
–2 147 483 648 to 2 147 483 647
–2 147 483 648 to 2 147 483 647
–64 to 64
0 (False), 1 (True)
0 (False), 1 (True)
Floating-point range and range of values according to IEEE 754
(single precision)
System Functions
3.3 Processing Quality Attributes
81