Function Control - Siemens 6MD85 Manual

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Basic Structure of the Function

2.3 Function Control

2.3
Function Control
Function control is used for:
Functions that do not contain stages or function blocks
Stages within functions
Function blocks within functions
NOTE
i
i
Simplifying functions and function control will be discussed in the following. The description also applies
to tripping stage control and function block control.
Functions can be switched to different operating modes. You use the parameter Mode to define whether you
want a function to run (On) or not (Off). In addition, you can temporarily block a function or switch it into test
mode for the purpose of commissioning (parameter Mode = Test).
The function shows the current status – such as an
The following explains the different operating modes and mechanisms and how you set the functions into
these modes. The function control is shown in
control is not discussed further in the individual function descriptions.
[losteurg-040411-01.tif, 1, en_US]
Figure 2-3
State Control
You can control the state of a function via the parameter Mode and the input Superordinate state.
You set the specified operating state of the function via the parameter Mode. The function mode can be set to
On, Off, and Test. The operating principle is described in
DIGSI 5
On-site operation at the device
Certain systems control protocols (IEC 61850, IEC 60870-5-103)
The possibility to adjust the superordinate state is limited. For test purposes, the complete device can set into
test mode.
40
General Control of a Function
Alarm – via the Health signal.
Figure
2-3. It is standardized for all functions. Therefore, this
Table
2-2. You can set the parameter Mode via:
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

6md86

Table of Contents