System Functions
3.1 Indications
Indications in
Log for parameter changes
Spontaneous indication window
(DIGSI 5)
Log for safety indications
Log for device-diagnostic indica-
tions
2
Log for communication indications
Overview of Displayed Quality Attributes
If values are shown on the device display or in DIGSI, the following quality attributes are different for meas-
ured values and metered values.
Table 3-2
IEC 61850
Detail Quality
-
Failure
Inaccurate
Bad Reference
Out of Range
1
Only online access
2
Only online access
3
Only online access
52
DIGSI 5 Information
Time stamp (date and time),
Relative time,
Entry number,
Function structure,
Name,
Value,
Quality,
Cause,
Number
Time stamp (date and time),
Relative time
Indication,
Value,
Quality,
Additional Information
Time stamp (date and time),
1
Indication number,
Indication
Time stamp (date and time),
Indication number,
Indication
Time stamp (date and time),
3
Indication number,
Indication
Measured Values
Validity
Good
Invalid
Questionable
X
X
X
X
X
Device Display Information
Time stamp (date and time),
Function structure,
Name,
Value
Time stamp (date and time),
Fault number,
Value
Time stamp (date and time),
Indication
Time stamp (date and time),
Indication
Time stamp (date and time),
Indication
Device Display/
Description
DIGSI
Value
The measured value is valid.
Fault
The device is defective. Contact
Support.
---
The measured value was not
calculated (for example, the
angle between current and
voltage if one of the 2 variables is
missing).
≈ Value
The measured value can be inac-
curate (for example, outside the
frequency-tracking range).
> Value
The measured value exceeds the
measuring range.
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017