Ups Output; Ups Environmental - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

PRODUCT SPECIFICATIONS
10−2
EATON Powerware
10.2.2

UPS Output

UPS Output Capacity
Output Voltage Regulation
Output Voltage Adjustment
(Nominal +/–3%)
Output Voltage Harmonic Content
Output Current
Output Voltage Balance
Output Voltage Phase
Displacement
Output Transients
Frequency Regulation
Synchronous to Bypass
Frequency Slew Rate
Load Compatibility
Overload Capability
10.2.3

UPS Environmental

Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
100% rated current
"1% (10% to 100% load)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
1.5% maximum THD (linear load)
5% maximum THD (nonlinear load)
See Table 3-4 on page 3−9 or Table 3-5 on page 3−10 for four UPM
models.
See Table 3-6 on page 3−11 or Table 3-7 on page 3−12 for three UPM
models.
3% for 100% maximum load imbalance (linear load)
3° for 100% maximum load imbalance (linear load)
"5% (10% to 100% load)
"0.1 Hz free running
+10% to −10% "3%
1 Hz per second maximum
0.9 pF Leading
0.8 pF Lagging
110% for 10 minutes
125% for 30 seconds
150% for 10 seconds
0 to 40°C (32 to 104°F) without derating. The recommended
operating temperature is 25°C (77°F).
Maximum 1500m (5000 ft) at 40°C without derating
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self-discharge)
5% to 95% maximum noncondensing
76 dB at a 1m distance, A weighted
Meets FCC Regulation 47, Part 15, for class A devices
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse
without damage and with no disturbance or adverse effect to the
critical load.
S
164201764 Rev 1 www.powerware.com