Figure 8-2. Sample Event History Log - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

COMMUNICATION
8−6
EATON Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
MODEL: POWERWARE 9395
CTO: TF12710000000
SERIAL:
MCU DSP:
70.81.14
MCU BOOTLOADER:
MCU PLD:
1.00
PMF 1 DSP:
80.81.14
PMF 1 BOOTLOADER:
PMF 1 PLD:
1.00
XSLOT CAN BRIDGE:
CSB DSP:
70.81.14
CSB BOOTLOADER:
DISPLAY:
1.06
TIME: 19:17:16 DATE: 03/23/2099
03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)
03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)
03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)
03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)
03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)
03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)
03/16/2099 21:25:25.850 N011: OUTPUT UNDER OR OVER FREQ OK (PM1)
...
03/23/2099 18:59:20.225 A199: BATTERIES DISCONNECTED (PM1)
ACTIVE ALARMS:
11 NOTICE: OUTPUT UNDER OR OVER FREQ (PM1)
12 ALARM: REMOTE EMERGENCY POWER OFF (MCU)
102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1)
103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1)
104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1)

Figure 8-2. Sample Event History Log

S
164201764 Rev 1 www.powerware.com
80.40
80.40
0.00
1.12