Figure 4-17. Distributed Bypass Wire Length - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

UPS SYSTEM INSTALLATION
Bypass Input to UPS Units
1A
2A
3A
4A
NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For proper
operation the following must be true:
1A = 2A = 3A = 4A
1B = 2B = 3B = 4B
NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference
between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%.
4−20
EATON Powerware

Figure 4-17. Distributed Bypass Wire Length

®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
UPS 1
Battery
UPS 2
Battery
UPS 3
Battery
UPS 4
Battery
S
164201764 Rev 1 www.powerware.com
Output from UPS Units
1B
2B
3B
4B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9395

Table of Contents