Figure 6-4. Path Of Current Through The Ups In Battery Mode - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

Bypass Input
Input
Breaker
Rectifier
(CB1
Input
K1
Breakers
Contactors
EATON Powerware
During a utility power failure, the rectifier no longer has an AC utility source from
which to supply the DC output current required to support the inverter. The input
contactor K1 opens and the battery instantaneously supplies energy to the battery
converter. The converter either bucks or boosts the voltage so that the inverter can
support the customer's load without interruption. If bypass is common with the
rectifier input, the backfeed protection contactor K5 also opens. The opening of
contactors K1 and K5 prevent system voltages from bleeding backwards through the
static switch and rectifier snubber components and re−entering the input source.
Bypass
Breaker
(CB4)
Static
Switch
Rectifier
Converter
Closed
Open

Figure 6-4. Path of Current Through the UPS in Battery Mode

If the input power fails to return or is not within the acceptance windows required for
normal operation, the battery continues discharging until a DC voltage level is reached
where the inverter output can no longer support the connected loads. When this
event occurs, the UPS issues another set of audible and visual alarms indicating
SHUTDOWN IMMINENT. Unless the rectifier has a valid AC input soon, the output
can be supported for only two minutes before the output of the system shuts down.
If the bypass source is available, the UPS transfers to bypass instead of shutting
down.
If at any time during the battery discharge the input power becomes available again,
contactors K1 and K5 close and the rectifier begins to supply DC current to the
converter and inverter. At this point, the unit returns to Normal mode. Depending on
the total load and the duration of the battery discharge, battery current limit alarms
may be seen for a short time due to the current required to recharge the battery.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
K5
Inverter
Battery
K2
Battery
Breaker
Battery
S
164201764 Rev 1 www.powerware.com
UNDERSTANDING UPS OPERATION
Output
K3
Main Power Flow
Trickle Current
Energized
De−Energized