Chapter 10
Figure 10Table 10

10.1 Model Numbers

10.2 Specifications
EATON Powerware

Product Specifications

The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.
Models
Powerware 9395−1100/1000 (four UPM)
Powerware 9395−1100/1100 (four UPM)
Powerware 9395−1100/650 (three UPM)
Powerware 9395−1100/750 (three UPM)
Powerware 9395−1100/825 (three UPM)
The following sections detail the input, output, environmental, and battery
specifications for the UPS.
10.2.1

UPS Input

Operating Input Voltage
Operating Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity
Battery Shunt Trip
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
Power Rating
1000 kVA
1100 kVA
650 kVA
750 kVA
825 kVA
480 Vac
50/60 Hz
See Table 3-4 on page 3−9 or Table 3-5 on page 3−10 for four UPM
models.
See Table 3-6 on page 3−11 or Table 3-7 on page 3−12 for three UPM
models.
Reduced for Generator
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
480 Vdc
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
48 Vdc
S
164201764 Rev 1 www.powerware.com
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
10−1