8.3. UPS System Output

Table 8-3: UPS System Output

Number of Output Phases
Rated Output Voltage
Total Voltage Harmonic Distortion
Rated Output Frequency
Output Frequency Variation
Slew Rate
Overload Capability at Ambient 40 °C
(on Inverter)
Overload Capability at Ambient 40 °C
(on Inverter, Stored Energy Mode)
Overload Capability at Ambient 40 °C
(on Bypass)
Output Current
Load Power Factor, (Rated)
Load Power Factor, (Permitted Range)
3 phases + N
220/380 V; 230/400 V; 240/415 V, configurable
100 % Linear Load < 1 %
100 % Non-Linear Load < 5 %
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
60 min 102-110 % load
10 min 111-125 %
60 sec 126-150 % load
300 ms > 150 % load
10 min 102-110 % load
60 sec 111-125 % load
300 ms > 125 % load
Continuous < 125 % load
10 ms 1000 % load
Note! Bypass fuses may limit the overload capability.
See Table
power and voltage on page 31
1.0
From 0.8 lagging to 0.8 leading
Eaton 93PR 500 kW UPS
User's and Installation Guide
3-5