Ups System Output; Table 8-3: Ups System Output - Eaton 93PR Installation And Operation Manual

Table of Contents

Advertisement

8.3. UPS System Output

Table 8-3: UPS System Output

Number of Output Phases
Rated Output Voltage
Total Voltage Harmonic Distortion
Rated Output Frequency
Output Frequency Variation
Slew Rate
Overload Capability at Ambien 30°C
(Ambient Temperature)
Overload Capability at Ambient 30°C
(Double Conversion Mode)
Overload Capability at Ambient 30°C
(on Inverter, Stored Energy Mode)
Overload Capability at Ambient 30°C
(on Bypass)
Output Current
Load Power Factor, (Rated)
Load Power Factor, (Permitted Range)
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
3 phases + N (Optional)
220/380 V; 230/400 V; 240/415 V, configurable
100% Linear Load < 1%
100% Non-Linear Load < 5%
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
10 min 125% load
60 min 102-110 % load
10 min 111-125 %
30 sec 126-150 % load
300 ms > 150 % load
1 min 102-110 % load
300 ms > 110 % load
Continuous < 115% load,
10 ms 1000% load
Note! Bypass fuses may limit the overload capability.
See
Table 3-6
Rated and Maximum Currents for Rated
Power and Voltage (unit:A)
1.0
From 0.8 lagging to 0.8 leading
123