Relay Interface Module Ii; Figure 8-4. Relay Interface Module Ii Customer Interface Connectors J1 Through J4 - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

8.9

Relay Interface Module II

EATON Powerware
An optional Relay Interface Module II (RIM II) uses relay contact closures to indicate
the operating status and alarm condition of the UPS system. The module uses a serial
interface line and may support up to eight critical loads. The RIM II can be
flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-4
shows the RIM II with its four 15-pin connectors labeled J1 through J4.

Figure 8-4. Relay Interface Module II Customer Interface Connectors J1 through J4

The RIM II can provide the status and alarm signals shown in Table 8-2.
Table 8-2. Customer Interface Connectors
Status
J1 through J4
UPS AVAILABLE
UPS OFFLINE
BATTERY WEAK
UTILITY FAILURE
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
Description
Pins 1 and 12
Contacts are closed when the UPS is operating in Normal mode
or ready to supply the load.
Pins 3 and 13
Contacts are open when the UPS is offline.
Contacts are closed when the UPS is operating in Normal mode.
Pins 5 and 14
Contacts are closed when approximately two minutes of battery
time is remaining before the critical load is lost.
Pins 6 and 15
Contacts are closed when Utility Failure is detected.
S
164201764 Rev 1 www.powerware.com