Multiple Ups Distributed Bypass Operation; Starting The Distributed Bypass System In Normal Mode - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

UPS OPERATING INSTRUCTIONS
7.4

Multiple UPS Distributed Bypass Operation

7−20
EATON Powerware
7.4.1

Starting the Distributed Bypass System in Normal Mode

To start the distributed bypass system:
1.
If the UPSs contain input breakers (CB1), verify that all input breakers are open.
2.
Close all Module Output Breakers (MOBs).
3.
Close all UPS input feeder circuit breakers.
4.
Close all UPS Bypass input feeder circuit breakers.
5.
Observe the UPS control panel displays becoming active, indicating logic power.
6.
On any UPS, press the
Status screen is displayed.
On the System Status screen, verify the UPS status is SHUTDOWN and the UPM
7.
status is OFFLINE.
8.
Close all battery breakers.
9.
If the UPSs contain input breakers (CB1), close all input breakers.
10. On the System Status screen, select the
11. Press the
CONTROLS
Control Command screen is displayed.
12. On the UPS Control Command screen, select
13. Press the
SELECT
If Auto Bypass is enabled (factory default), the critical load is immediately
supplied by the bypass source in Bypass mode from all UPSs, until the inverter
turns on and the UPSs transfer to Normal mode. The status indicator on the UPS
control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled,
the UPS outputs remain off until the UPSs transfer to Normal mode.
14. Verify the following messages display sequentially on the UPS status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
ONLINE, CHARGING
The rectifier and inverter turn on. The inverter continues to ramp up to full
voltage.
Once the inverter reaches full voltage, all UPS output contactors (K3) close and
the bypass circuits open. Power is now supplied to the critical load in Normal
mode from all UPSs. It takes approximately one minute for the UPSs to achieve
Normal mode.
The
NORMAL
The UPM status indicates ONLINE, CHARGING.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
pushbutton on the main menu bar. The System
CONTROLS
pushbutton on the System Status menu bar. The UPS
pushbutton on the UPS Command menu bar.
status indicator is illuminated. The UPS status indicates ONLINE.
S
164201764 Rev 1 www.powerware.com