Table 7-5. Command Menu Operation
Function
Subfunction
UPS Control Commands
Go to Normal
Go to Bypass
Load Off
Bypass Commands
Go to Bypass
Go to Normal
Load Off
Charger Control
Commands
Charger On
Charger Off
UPM Control
Commands
UPM On
UPM Off
UPM Go to Normal
Charger On
Charger Off
EATON Powerware
Table 7-4. Typical System Status Messages
Function
UPS
Bypass
Maintenance Bypass
Charger
UPM (during startup)
UPM 1
UPM 2
UPM 3
UPM 4 (not displayed on three UPM model)
Operation
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Displays the Load Off screen (see paragraph 7.2.8).
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command or proceed to further command screens.
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Normal mode.
Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode.
Displays the Load Off screen (see paragraph 7.2.8).
Use the up or down arrow pushbutton to highlight the command function desired, then press the
SELECT pushbutton to execute the command.
Turns the battery charger on.
Turns the battery charger off
Use the up or down arrow pushbutton to highlight the command function desired, then press the
CONTROLS pushbutton to execute the command.
Turns the UPM on without transferring the load to Normal mode. The Load is on bypass.
Transfers the load to bypass and turns the UPM off.
Turns the UPM on and transfers the load to Normal mode.
Turns the battery charger on.
Turns the battery charger off
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
UPS OPERATING INSTRUCTIONS
Message
Shutdown; Bypass; Online
Off; On; Available
Off; On
Charger Off; Charging
DC Starting, Charger Off; DC Starting, Close Battery
Breaker; Inverter Starting; Inverter Syncing; Ready; Online
Offline; Shutdown, Charger Off; Ready; Ready, Charging;
Online, Charger Off; Online, Charging
S
164201764 Rev 1 www.powerware.com
7−9