Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825
Terminal Function
AC Input to UPM Section
AC Output from UPM Section
DC Input to UPM Section
Table 3-9. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Flat Washer
Conical Washer
Nut
EATON Powerware
Terminal
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
Size
Quantity
M8
36
M8
36
M8
36
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
Function
Bus Landing
Phase A
3 – stud mounting
Phase B
3 – stud mounting
Phase C
3 – stud mounting
Phase A
3 – stud mounting
Phase B
3 – stud mounting
Phase C
3 – stud mounting
Neutral
3 – stud mounting
6 – stud mounting
Positive
(2 per UPM)
6 – stud mounting
Negative
(2 per UPM)
Terminals Used On
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
UPM AC Input, UPM Battery Input, UPM AC
Output, and Neutral
S
164201764 Rev 1 www.powerware.com
UPS INSTALLATION PLAN AND UNPACKING
Tightening Torque
Nm (lb ft)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
12 (8.3)
Eaton Part Number
180500036−080
180500037−080
180200001−05
Stud
M8
M8
M8
M8
M8
M8
M8
M8
M8
3−13