Powerware 9395 UPS ® 1000–1100 kVA Installation and Operation Manual For use with Three UPM (650–825 kVA) and Four UPM (1000–1100 kVA) UPS Models...
This is a product for restricted sales distribution to informed partners (EN/IEC 62040−2). Installation restrictions or additional measures may be needed to prevent electromagnetic disturbances. Eaton, Powerware, X−Slot, LanSafe, PowerXpert, and Powerware HotSync are registered trademarks and ConnectUPS is a trademark of Eaton Corporation or its subsidiaries and affiliates. IBM and AS/400 are registered trademarks of International Business Machines Corporation.
Page 4
..................4.13 Completing the Installation Checklist Installing Options and Accessories Installing an Optional Powerware Hot Sync CAN Bridge Card Installing Distributed Bypass Control Wiring Installing an Optional Remote Monitor Panel II Installing an Optional Relay Interface Module II...
Page 5
................Powerware LanSafe Power Management Software Remote Notification .
Page 7
List of Figures Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA) Figure 1-2. Powerware 9395 Three UPM UPS (650–825 kVA) Figure 3-1. UPS Cabinet Dimensions (Front View) Figure 3-2. UPS Cabinet Dimensions (Right Side View) Figure 3-3. ISBM Section Dimensions (Front View) Figure 3-4.
Page 8
TABLE OF CONTENTS Figure 5-1. Powerware Hot Sync CAN Bridge Card Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections Figure 5-3. Distributed Bypass System Can and Pull−Chain Simplified Interface Wiring Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs Figure 5-5.
The UPS is available as a single unit or an optional multiple unit distributed bypass system (see paragraph 1.2.4). The Powerware 9395 online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
9395 UPS (1000–1100 kVA) Installation and Operation Manual ISBM SECTION Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA) The UPS has many standard features that provide cost-effective and consistently reliable power protection. The descriptions in this section provide a brief overview of the UPS standard features.
ISBM SECTION Figure 1-2. Powerware 9395 Three UPM UPS (650–825 kVA) 1.1.3 Customer Interface Building Alarm Monitoring – Up to five inputs in the UPS are available to connect the facility’s alarm system contacts. Some system configurations may limit the number of inputs available.
Operation remains the same as the original UPS. Inherent Redundancy To deliver greater reliability, the Powerware 9395 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
A ConnectUPS−X Web/SNMP Card is required in an X−Slot communication bay. An optional Powerware Environmental Monitoring Probe (EMP) is required for temperature/humidity monitoring. See Chapter 8, Communication," for additional information on monitoring and communication features.
Remote Emergency Power−off (REPO) control, RMP II, or X−Slot communication cards. This manual describes how to install and operate the Powerware 9395 1000–1100 kVA UPS. Read and understand the procedures described in this manual to ensure trouble−free installation and operation. In particular, be thoroughly familiar with the REPO procedure (see paragraph 7.3.11 on page 7−18).
(WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Refer to the Powerware 9390 and 9395 Sync Control Installation and Operation Manual for the following additional information: Installation instructions, including site preparation, planning for installation, and wiring and safety information.
Scheduling initial startup Regional locations and telephone numbers A question about any of the information in this manual A question this manual does not answer Please call the Eaton Help Desk for Powerware products at: 1−800−843−9433 United States: 1−800−461−9166 ext 260...
Do not install or operate the UPS system close to gas or electric heat sources. D A N G E R W A R N I N G C A U T I O N 164201764 Rev 1 www.powerware.com 2−1...
Page 18
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser. C A U T I O N 164201764 Rev 1 www.powerware.com...
Failure to follow guidelines may void your warranty. The UPS equipment operating environment must meet the weight requirements shown in Table 3-1 and the size requirements shown in Figure 3-1 through Figure 3-10. Dimensions are in millimeters (inches). 164201764 Rev 1 www.powerware.com 3−1...
Page 22
EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual For Field Installed UPM (FI−UPM) weights and dimensions, refe to the Powerware 9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.8 on page 1−7. Table 3-1. UPS Cabinet Weights Model Powerware 9395−1100/1000...
3−6 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual Figure 3-8. ISBM Section Center of Gravity Figure 3-9. UPM Section Center of Gravity 164201764 Rev 1 www.powerware.com Dimensions are in millimeters [inches]. Dimensions are in millimeters [inches].
In a common battery system, single and multiple UPMs are powered from one common battery source. In a separate battery system, multiple UPMs are each powered from separate battery sources. A Field Installed UPM (FI−UPM) is always designated as UPM 4. 164201764 Rev 1 www.powerware.com...
Page 29
Table 3-4. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100 – Common Battery Basic Unit Rating Input and Output Voltage AC Input to UPS Rectifier (0.98 Minimum pF) Full load current plus battery recharge current...
Page 30
UPS INSTALLATION PLAN AND UNPACKING Table 3-5. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000, and 9395−1100/1100 – Separate Battery Basic Unit Rating Input and Output Voltage AC Input to UPS Rectifier (0.98 Minimum pF) Full load current plus battery recharge current...
Page 31
Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 – Common Battery Basic Unit Rating Input and Output Voltage AC Input to UPS Rectifier (0.98 Minimum pF) Full load current plus battery recharge current...
Page 32
UPS INSTALLATION PLAN AND UNPACKING Table 3-7. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 – Separate Battery Basic Unit Rating Input and Output Voltage AC Input to UPS Rectifier (0.98 Minimum pF)
Page 33
Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 Terminal Function E1A (UPM 1) E1A (UPM 2) E1A (UPM 3) E1A (UPM 4 – Four UPM Model)
Page 34
UPS INSTALLATION PLAN AND UNPACKING Table 3-10. UPS External Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 Terminal Function Terminal AC Input to UPS Rectifier AC Input to Bypass...
Page 35
Thomas & Betts As required Thomas & Betts Thomas & Betts Thomas & Betts Thomas & Betts Thomas & Betts Thomas & Betts 164201764 Rev 1 www.powerware.com UPS INSTALLATION PLAN AND UNPACKING Eaton Part Number 180190078−087 180190078−115 180500036−100 180500036−120 180500037−100 180500037−120...
Page 36
AC Input to Bypass and Output (Five Wire) (A, B, C, Neutral, Ground) Battery (Positive, Negative, Ground) Number of Wires Minimum Conduit in Conduit Trade Size See Note 3-1/2 See Note See Note 164201764 Rev 1 www.powerware.com Number of Conduits...
Page 37
80% Rated 1600A 100% Rated 1200A C A U T I O N Output Rating Load Rating 480V 80% Rated 1600A 100% Rated 1600A 80% Rated 2000A 100% Rated 1600A 80% Rated 1600A 100% Rated 1000A 164201764 Rev 1 www.powerware.com 3−17...
Page 38
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current. Input Rating 480V 2500A 3000A 2000A Input Rating (each UPM) 480V 700A 164201764 Rev 1 www.powerware.com...
REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG. EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS INSTALLATION PLAN AND UNPACKING W A R N I N G 164201764 Rev 1 www.powerware.com 3−19...
DO NOT install both a source neutral and a bonding jumper. The UPS cannot be installed in a high−resistance ground application. MOBs with dual auxiliary contacts are to be provided by the customer. Table 3-15 on page 3−17 lists the recommended rating for the MOBs. 164201764 Rev 1 www.powerware.com...
(see Figure 4-15 on page 4−17). Do not remove the debris shields until installation is complete. UPS INSTALLATION PLAN AND UNPACKING W A R N I N G C A U T I O N C A U T I O N C A U T I O N 164201764 Rev 1 www.powerware.com 3−21...
NOTE While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. 164201764 Rev 1 www.powerware.com...
If these instructions are not followed, damage to the wiring channel and wiring will occur. W A R N I N G " 10° during installation. W A R N I N G C A U T I O N 164201764 Rev 1 www.powerware.com 4−1...
Remove the three bolts securing the right side shipping bracket to the cabinet and three bolts securing the bracket to the pallet (see Figure 4-2 or Figure 4-4). Remove the right side shipping bracket. Left Side Shipping Bracket Front Door Pallet 164201764 Rev 1 www.powerware.com...
Carefully lower the cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4.3. EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION Shipping Bracket Bolts Shipping Bracket Bolts 164201764 Rev 1 www.powerware.com 4−3...
Retain the hardware for later use. Remove the screws securing the corner channel and remove the channel (see Figure 4-5). Retain the hardware for later use. UPS SYSTEM INSTALLATION Shipping Bracket Bolts Shipping Bracket Bolts 164201764 Rev 1 www.powerware.com 4−5...
Reinstall the corner channel (see Figure 4-5) and secure using the retained hardware. Reinstall the left middle panel (see Figure 4-5) and secure using the retained hardware. UPM Section C A U T I O N 164201764 Rev 1 www.powerware.com...
AC Input to UPMs terminals. See Figure 4-8 on page 4−11 for terminal locations. Screw from Kit Screw from Kit Back Top View Rear Bracket UPM Section Base Screw from Kit 164201764 Rev 1 www.powerware.com Section Top...
Page 53
(see Figure 4-9 on page 4−12). This hardware is used by an Eaton Customer Service Engineer to install a Field Installed UPM (FI−UPM). EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION 164201764 Rev 1 www.powerware.com 4−9...
Page 54
26. If installing a battery system, proceed to paragraph 4.6; otherwise, proceed to Step 27. 27. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7; otherwise, proceed to paragraph 4.8. 164201764 Rev 1 www.powerware.com...
CB4 charging handle to provide operating clearance for the handle. DC Input to UPMs – (E5) (See Figure 4-10 for detail.) DC Input to UPMs + (E4) (See Figure 4-10 for detail.) 164201764 Rev 1 www.powerware.com 4−11...
UPM 2 (2E5A) – DC Input to UPMs Cable 2G3 Black Cable 3G3 Black UPM 3 (3E5A) Cable 3G3 Black Phase A (E9A) AC Output Phase B (E10A) from UPMs Phase C (E11A) Neutral from UPMs (E12A) 164201764 Rev 1 www.powerware.com 4−13...
NOTE FI−UPM installation is not applicable to a three UPM model. If installing a four UPM model, install the FI−UPM using the instructions in the Powerware 9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.8 on page 1−7. After the FI−UPM is installed, proceed to paragraph 4.6 if installing a battery system;...
Page 61
(Remove shield before operating system.) ISBM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) UPM Section Front Figure 4-15. ISBM and UPM Section Debris Shields EATON Powerware 164201764 Rev 1 www.powerware.com 4−17 ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual...
Page 62
9395 UPS (1000–1100 kVA) Installation and Operation Manual Front through TB3 Wiring and X−Slot Connections (Remove panels to drill or punch conduit holes.) Front Figure 4-16. ISBM Section Conduit and Wire Entry Locations 164201764 Rev 1 www.powerware.com Interface Entry Conduit Landings for TB1...
Page 63
3.2.2 on page 3−8 for wiring and termination requirements. 10. Proceed to paragraph 4.8.2. EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION C A U T I O N 164201764 Rev 1 www.powerware.com 4−19...
Page 65
– (E5) (See Figure 4-20 or Figure 4-21 for Detail BB.) Neutral (E12) EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual Figure 4-18. ISBM Section Power Terminal Locations UPS SYSTEM INSTALLATION ISBM 164201764 Rev 1 www.powerware.com 4−21...
Page 66
Figure 4-19. ISBM Section Power Terminal Detail AA Front ‘ Phase C (E3) AC Input to Phase B (E2) UPS Rectifier Phase A (E1) Phase A (E6) AC Input to Phase B (E7) UPS Bypass Phase C (E8) 164201764 Rev 1 www.powerware.com...
Reinstall the left front panel removed in paragraph 4.8.1, Step 1 on page 4−16 and secure with the retained hardware. EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION C A U T I O N 164201764 Rev 1 www.powerware.com 4−23...
Page 68
DC Input from Battery + (E4) DC Input from Battery – (E5) Figure 4-20. ISBM Section Power Terminal Detail BB – Common Battery 4−24 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual Front Section B–B 164201764 Rev 1 www.powerware.com...
Page 69
DC Input from Battery – (E5) (UPM 3) Figure 4-21. ISBM Section Power Terminal Detail CC – Separate Battery EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION Section B–B 164201764 Rev 1 www.powerware.com 4−25...
X−Slot connections only, proceed to paragraph 4.9.3; otherwise, proceed to Step 10. 10. Reinstall the top internal safety shield panel and secure with the retained hardware. W A R N I N G W A R N I N G 164201764 Rev 1 www.powerware.com...
Page 71
EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual TB1 and TB2 (See Figure 4-23 for detail.) 164201764 Rev 1 www.powerware.com UPS SYSTEM INSTALLATION X−Slot Communication Bays (See Figure 4-28 on page 4−33 for detail.) (See Figure 4-25 on page 4−30 for terminal...
Page 72
Input: Programmable UPS alarm, activated by a remote dry contact closure. Default function set for on generator. Input: Programmable UPS alarm, activated by a remote dry contact closure. Default function set for maintenance bypass. 164201764 Rev 1 www.powerware.com...
Page 73
EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION X−Slot Communication Bays See Figure 4-25 for terminal assignments. Alarm Relay NC Alarm Relay Common Alarm Relay NO Alarm Relay Common 164201764 Rev 1 www.powerware.com 4−29...
Page 74
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally−closed REPO contact is not used. Figure 4-25. Terminal Blocks TB1, TB2, and TB3 Connector Assignments 4−30 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual 164201764 Rev 1 www.powerware.com REPO NC REPO Return REPO NO REPO Return Battery Aux...
12. If wiring X−Slot connections, proceed to paragraph 4.9.3; otherwise, proceed to Step 13. 13. Close the door and secure the latch. EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION 164201764 Rev 1 www.powerware.com 4−31...
X−Slot Communication Bay 1 X−Slot Communication Bay 3 Figure 4-28. X−Slot Communication Bays EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual UPS SYSTEM INSTALLATION X−Slot Communication Bay 2 X−Slot Communication Bay 4 164201764 Rev 1 www.powerware.com 4−33...
Remove the door. Remove the retaining screw located inside the door at the bottom hinge pivot point, then lift the door off. Retain the hardware for later use. REPO Switch (Front View) Figure 4-29. REPO Switch Contact Block (Back View, Faceplate Removed) 164201764 Rev 1 www.powerware.com...
NOTE The Installation Checklist MUST be completed prior to starting the UPS system for the first time. UPS SYSTEM INSTALLATION 1 (NC) 2 (Return) UPS TB1 3 (NO) Twisted Wires 4 (Return) 164201764 Rev 1 www.powerware.com 4−37...
- The debris shields covering the UPS cabinet ventilation grills are removed. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4−38 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual 164201764 Rev 1 www.powerware.com...
- Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. EATON Powerware 164201764 Rev 1 www.powerware.com 4−39 ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual...
Module II, or a Supervisory Contact Module II to the UPS. Figure 5-1. Powerware Hot Sync CAN Bridge Card NOTE Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN cards are not supported and will cause system conflicts.
Page 86
120 Vac for the RMP II, RIM II, or SCM II should be provided from the critical bus by facility planners or the customer. Install wiring from the Powerware Hot Sync CAN Bridge Card in accordance with the following instructions: Parallel system wiring (see paragraph 5.2)
MOBs. See Figure 5-6 on page 5−7 and Table 5-4 on page 5−8 for wiring information. NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
AUX 2 AUX 2 UPS 2 UPS 3 (If Installed) INSTALLING OPTIONS AND ACCESSORIES Twisted Pair Twisted Pair UPS 4 CAN Bridge Card J3 (If Installed) MOB 4 AUX 1 AUX 2 UPS 4 (If Installed) 164201764 Rev 1 www.powerware.com 5−7...
Page 92
MOB 4 Aux 2 Com Function MOB Open Alarm Pull Chain Pull Chain Common MOB Open Alarm Pull Chain Pull Chain Common MOB Open Alarm Pull Chain Pull Chain Common MOB Open Alarm Pull Chain Pull Chain MOB Common 164201764 Rev 1 www.powerware.com...
Install wiring between the UPS and RMP II. See Figure 5-2 and Table 5-1 for the Powerware Hot Sync CAN Bridge Card terminal location and wiring information, and Figure 5-7, Figure 5-8, and Table 5-5 for the RMP II terminal location and wiring information.
® 9395 UPS (1000–1100 kVA) Installation and Operation Manual NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass.
10. Restart the UPS. See Chapter 7, UPS Operating Instructions," for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
Install wiring between the UPS and SCM II. See Figure 5-2 and Table 5-1 for the Powerware Hot Sync CAN Bridge Card terminal location and wiring information, and Figure 5-10, Figure 5-8, and Table 5-5 for the SCM II terminal location and wiring information.
® 9395 UPS (1000–1100 kVA) Installation and Operation Manual NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment.
9395 UPS (1000–1100 kVA) Installation and Operation Manual Figure 5-12 through Figure 5-14 show the dimensions of the RMP II, the RIM II, and the SCM II. Figure 5-12. Remote Monitor Panel II Dimensions INSTALLING OPTIONS AND ACCESSORIES 164201764 Rev 1 www.powerware.com 5−15...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. 5−16 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual Figure 5-13. Relay Interface Module II Dimensions 164201764 Rev 1 www.powerware.com...
9395 UPS (1000–1100 kVA) Installation and Operation Manual Understanding UPS Operation The Powerware 9395 UPS is a continuous−duty, solid-state, transformerless (at 480 Vac), three−phase, true online system that provides conditioned and uninterruptible AC power to the UPS system’s output and critical load.
UPS to successfully support its applied loads. Modes The Powerware 9395 UPS supports a critical load in three different modes of operation: In Normal mode, the critical load is supplied by the inverter, which derives its power from rectified utility AC power.
Static Static Switch Switch Inverter Inverter Battery Converter Main Power Flow Main Power Flow Trickle Current Trickle Current Battery Battery Breaker Breaker Energized Energized De−Energized De−Energized Battery C A U T I O N 164201764 Rev 1 www.powerware.com Output 6−3...
DC power that the inverter converts to AC power. Figure 6-4 shows the path of electrical power through the UPS system when operating in Battery mode. Inverter Main Power Flow Trickle Current Energized De−Energized 164201764 Rev 1 www.powerware.com Output...
Single Unit Four UPM – Reverse Transfer Dual-Feed Separate Battery System Single Unit Three UPM – Reverse Transfer Dual-Feed Common Battery System Single Unit Three UPM – Reverse Transfer Dual-Feed Separate Battery System Simplified Dual−Feed UPS with Maintenance Bypass Panel 164201764 Rev 1 www.powerware.com...
UPMs online than required to support the load. Multiple UPS Parallel System Modes Similar to the single UPS system, the Powerware 9395 UPS parallel system supports a critical load in three different modes of operation. The standard operation...
Figure 6-11 shows the path of electrical power through the parallel system when operating in Bypass mode. UPS Input UPS 1 UPS 2 UPS 3 UPS 4 Breakers Closed Open Tie Cabinet UPS 1 Output UPS 2 Output UPS 3 Output UPS 4 Output Output to Critical Load 164201764 Rev 1 www.powerware.com...
UPMs online to support the connected load. When this event occurs, the system shuts down. If the bypass source is available, the system transfers to bypass instead of shutting down. EATON Powerware 164201764 Rev 1 www.powerware.com 6−15 ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual...
UPS automatically runs a battery test and the correct battery runtime displays. The controls and indicators identified and described in this section are used to control and monitor UPS operation. Figure 7-1 shows the UPS controls and indicators. ISBM 164201764 Rev 1 www.powerware.com 7−1...
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 7.3 for use of the operational controls. When the UPS powers up, the screen displays the Eaton | Powerware logo as shown in Figure 7-2. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
LCD in the UPS status area. This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. UPS OPERATING INSTRUCTIONS 164201764 Rev 1 www.powerware.com 7−3...
BYPASS EVENTS The UPS status area automatically scrolls between the Powerware model number, current date and time, active alarms, active notices, and load percent and battery runtime for the UPS. The top line of display blinks while scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible horn.
System Setup Level 0 Screen. No password is necessary to access Level 0 functions. Use the up or down arrow pushbutton to highlight the setup function screen desired, then press the SELECT pushbutton to display the function screen. 164201764 Rev 1 www.powerware.com...
Page 131
When finished making changes, use the left or right arrow pushbutton to highlight SAVE and the up or down arrow pushbutton to select YES. To complete the save function and return to the System Setup screen, select the return arrow pushbutton 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS Once the setting is saved, the System...
Table 7-5 describes the control functions and provides instructions to access and use the command menu screens. For detailed information about using the System Controls, see paragraph 7.3. SYSTEM STATUS SHUTDOWN AVAILABLE CONTROLS Figure 7-5. Typical System Status Screen pushbutton to display the CONTROLS 164201764 Rev 1 www.powerware.com...
Page 133
Off; On; Available Off; On Charger Off; Charging DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting; Inverter Syncing; Ready; Online Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online, Charger Off; Online, Charging 164201764 Rev 1 www.powerware.com 7−9...
Control Command screen. This screen allows the LOAD OFF process to be aborted if the LOAD OFF pushbutton was pressed accidentally. For Load Off procedures, see paragraph 7.3.10 on page 7−17. TO TURN OFF LOAD CANCEL Figure 7-6. Load Off Screen LOAD OFF 164201764 Rev 1 www.powerware.com...
It takes approximately one minute for the UPS to achieve Normal mode. status indicator is illuminated. The UPS status indicates ONLINE. NORMAL The UPM status indicates ONLINE, CHARGING. UPS OPERATING INSTRUCTIONS command. GO TO NORMAL 164201764 Rev 1 www.powerware.com 7−11...
If the UPS contains input breaker CB1, close input breaker CB1. On the System Status screen, select the On the UPS Control Command screen, select the C A U T I O N command. BYPASS GO TO BYPASS command. command. UPM 1 164201764 Rev 1 www.powerware.com...
Page 137
System Status menu bar. The UPM 1 CONTROLS pushbutton on the UPM 1 Command menu bar. SELECT to start UPM 2. UPM 2 to start UPM 3. UPM 3 to start UPM 4. UPM 4 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS UPM ON 7−13...
The UPS status indicates ONLINE. NORMAL The UPM status indicates ONLINE. C A U T I O N command. BYPASS GO TO BYPASS W A R N I N G command. GO TO NORMAL 164201764 Rev 1 www.powerware.com...
CONTROLS pushbutton on the System Status menu bar. The UPM CONTROLS pushbutton on the UPM Command menu bar. SELECT The input, output, and battery contactors 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS command. command. UPM 1 UPM OFF UPM OFF...
Control Command screen is displayed. On the Charger Control Command screen, select Press the pushbutton on the Charger Command menu bar. SELECT W A R N I N G command. CHARGER CHARGER ON command. CHARGER CHARGER OFF 164201764 Rev 1 www.powerware.com...
CONTROLS pushbutton on the System Status menu bar. The UPS or CONTROLS LOAD OFF pushbutton on the Command menu bar. SELECT 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS controls the UPS output by pushbutton, follow the procedure or the command.
Load Off menu bar, and hold for CANCEL C A U T I O N pushbutton, follow the procedure LOAD OFF W A R N I N G pushbutton switch. In an REPO C A U T I O N 164201764 Rev 1 www.powerware.com...
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. Deactivated Unlock pushbutton to release Figure 7-7. REPO Operation UPS OPERATING INSTRUCTIONS C A U T I O N 164201764 Rev 1 www.powerware.com 7−19...
UPSs. It takes approximately one minute for the UPSs to achieve Normal mode. status indicator is illuminated. The UPS status indicates ONLINE. NORMAL The UPM status indicates ONLINE, CHARGING. pushbutton on the main menu bar. The System command. GO TO NORMAL 164201764 Rev 1 www.powerware.com...
CONTROLS pushbutton on the Bypass Command menu bar. SELECT status indicator is illuminated. The Bypass status indicates ON. The pushbutton on the main menu bar. The System CONTROLS 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS command. GO TO BYPASS 7−21...
Page 146
UPS is ready to transfer to the Normal mode and supply the critical load. command. command. UPM 1 UPM ON to start UPM 2. UPM 2 to start UPM 3. UPM 3 to start UPM 4. UPM 4 164201764 Rev 1 www.powerware.com...
System Status menu bar. The UPS CONTROLS pushbutton on the UPS Command menu bar. SELECT status indicator is illuminated. The UPS status indicates ONLINE. 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS command. GO TO BYPASS GO TO NORMAL...
UPM OFF The input, output, and battery contactors to shut down UPM 2. UPM 2 to shut down UPM 3. UPM 3 to shut down UPM 4. UPM 4 W A R N I N G 164201764 Rev 1 www.powerware.com...
The System Status CONTROLS CHARGER pushbutton on the System Status menu bar. The Charger CONTROLS pushbutton on the Charger Command menu bar. SELECT 164201764 Rev 1 www.powerware.com UPS OPERATING INSTRUCTIONS UPM OFF command. CHARGER ON command. CHARGER OFF...
Load Off menu bar, and hold for CANCEL C A U T I O N pushbutton by following the LOAD OFF W A R N I N G or the command. BYPASS LOAD OFF 164201764 Rev 1 www.powerware.com...
LOAD OFF CANCEL C A U T I O N pushbutton by following the LOAD OFF W A R N I N G pushbutton switch. In an REPO C A U T I O N 164201764 Rev 1 www.powerware.com 7−27...
Page 152
Restart the UPSs by following the procedure in paragraph 7.4.1 on page 7−20 or 7.4.2 on page 7−21. Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. C A U T I O N W A R N I N G 164201764 Rev 1 www.powerware.com...
9395 UPS (1000–1100 kVA) Installation and Operation Manual Communication This chapter describes the communication features of the Powerware 9395 UPS and provides information about connecting hardware and using Terminal mode. For terminal wiring information, see paragraph 3.2.3 on page 3−19 and paragraph 4.9 on page 4−26.
Powerware 9395 UPS: Proactive monitoring, called Anomaly Detection, automatically analyzes the status of the Powerware 9395 UPS on a daily basis. All data gathered from the unit, current and historical, is analyzed at the Customer Reliability Center (CRC) for trending issues.
9395 UPS (1000–1100 kVA) Installation and Operation Manual The eNotify Service relies on a ConnectUPS−X Web/SNMP Card (or Power Xpert card) installed with the UPS sending one−way status and event e−mails to Powerware Remote Monitoring servers that analyze and store the data. Those servers also take the appropriate actions of sending notifications and reports.
To remotely control the UPS or view UPS information, use the Escape key legend to control the function normally controlled by the control panel softkeys. See paragraph 7.2 on page 7−2, Using the Control Panel," for instructions on navigating the control panel. 164201764 Rev 1 www.powerware.com...
Year (4 digits) Hour (2 digits) Minute (2 digits) Second (2 digits) Hundredths of Second (3 digits) Keyword (ALARM, NOTICE, COMMAND, or STATUS) System Diagnostic Information Carriage Return Character (ASCII 13) Line Feed (ASCII 10) 164201764 Rev 1 www.powerware.com COMMUNICATION 8−5...
The RMP II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-3 shows an RMP II front panel. Figure 8-3. Remote Monitor Panel II Front Panel COMMUNICATION C A U T I O N 164201764 Rev 1 www.powerware.com 8−7...
Page 160
DC voltage is approaching its low limit. This indicator is accompanied by a horn. 8−8 EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual The RMP II contains a local horn and the backlit status indicators listed in Table 8-1. 164201764 Rev 1 www.powerware.com...
Pins 5 and 14 Contacts are closed when approximately two minutes of battery time is remaining before the critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. COMMUNICATION 164201764 Rev 1 www.powerware.com 8−9...
NO REDUNDANCY TB2-4 through TB2-6 ON GENERATOR TB2-7 through TB2-9 BYPASS NOT AVAILABLE TB2-10 through TB2-12 ON BATTERY TB2-13 through TB2-15 UPS ALARM TB2-16 through TB2-18 ON BYPASS TB2-19 through TB2-21 SHUTDOWN IMMINENT TB2-22 through TB2-24 164201764 Rev 1 www.powerware.com...
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock is reduced if such grounds are removed during installation and maintenance. When replacing batteries, use the same number of sealed, lead-acid batteries. W A R N I N G 164201764 Rev 1 www.powerware.com 9−1...
(see Figure 4-2 on page 4−3). Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet. Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from the cabinet. 164201764 Rev 1 www.powerware.com...
To remove the filter: a. Remove one top screw and two bottom screws securing the FI−UPM front panel (refer to the Powerware 9395 Field Installed UPM Mechanical Installation Manual). Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
NOTE There is no manual DC disconnect device within the UPS. Install batteries in accordance with the battery and battery system manufacturer’s instructions. UPS MAINTENANCE 164201764 Rev 1 www.powerware.com 9−5...
UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk for Powerware products (see page 1−8). W A R N I N G...
The UPS is housed in a free-standing cabinet, divided into two sections with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings. Models Powerware 9395−1100/1000 (four UPM) Powerware 9395−1100/1100 (four UPM) Powerware 9395−1100/650 (three UPM) Powerware 9395−1100/750 (three UPM) Powerware 9395−1100/825 (three UPM)
Meets FCC Regulation 47, Part 15, for class A devices Electrostatic Discharge (ESD) Meets IEC 801-2 specifications. Withstands up to 25 kV pulse Immunity without damage and with no disturbance or adverse effect to the critical load. 164201764 Rev 1 www.powerware.com...
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, a Delaware Corporation ( Eaton"). LIMITED WARRANTY: This limited warranty (this Warranty") applies only to the original end−user (the End−User") of the Powerware Three−Phase UPS Products (the Product") and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Eaton for resale to an End−User.
Page 172
WARRANTY This page intentionally left blank. W−2 EATON Powerware 164201764 Rev 1 www.powerware.com ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual...