Figure 4-27. Typical Battery Interface Connection - Common Battery System; Figure 4-28. Typical Battery Interface Connection - Separate Battery System - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

UPS SYSTEM INSTALLATION
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
Battery Aux
Battery Aux Return
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip −
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
4−32
EATON Powerware
Battery Aux
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
Figure 4-26. Typical Battery Interface Connection – Common Battery System
UPS
TB1
5
6
7
8
Figure 4-27. Typical Battery Interface Connection – Separate Battery System
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
UPS
TB1
5
6
7
48 Vdc
8
UPM 1
Battery
Battery
Disconnect
Disconnect
ST
48 Vdc
S
164201764 Rev 1 www.powerware.com
Battery
Disconnect
ST
UPM 2
UPM 3
Battery
Disconnect
ST
ST
UPM 4
Battery
Disconnect
ST