Preliminary Installation Information

4.2

Unloading the UPS Sections from the Pallet

EATON Powerware

UPS System Installation

Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
S
Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and
installation notes.
S
Do not tilt the cabinets more than
S
Remove the conduit landing plates to add conduit landing holes as required. Plate
material is 16 gauge steel (1.5 mm/0.06" thick).
S
If perforated floor tiles are required for ventilation, place them in front of the UPS.
The ISBM and UPM sections are bolted to separate wooden pallets supported by
wood skids. To remove the pallets:
The UPS sections are heavy (see Table 3-1 on page 3−2). If unpacking and unloading instructions are not
closely followed, the cabinets may tip and cause serious injury.
S
Do not tilt cabinets more than 10° from vertical.
S
Lift the cabinets only with a forklift or damage may occur.
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the
cabinet:
S
Lift and move the UPM section using only the front or rear forklift slots.
S
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.
S
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
S
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.
S
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
S
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
W A R N I N G
"
10° during installation.