Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual page 31

1000–1100 kva
Table of Contents

Advertisement

Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and
9395−1100/825 – Common Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
A
B
C
NOTE Callout letters
,
,
, and
EATON Powerware
D
map to Figure 6-7 on page 6−9.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
UPS INSTALLATION PLAN AND UNPACKING
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Total Amps
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
AWG or kcmil
(each)
S
164201764 Rev 1 www.powerware.com
Rating 50/60 Hz
650
750
591
682
480/480
480/480
480/480
891
1028
1130
500
(4)
782
902
500
(4)
782
902
500
(5)
1280
1502
1600
500
(6)
782
902
500
(4)
782
902
500
(5)
4/0
(1)
825
750
992
992
992
992
3−11