Table 5-1. Powerware Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
EATON Powerware
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual

Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections

Name
Description
1
Alarm
Programmable UPS alarm. Activated by a remote dry contact closure.
2
Alarm Return
3
Alarm Relay NC
Normally-closed contact opens when UPS is on bypass.
4
Alarm Relay Com Bypass contact return.
5
Alarm Relay NO
Normally-open contact closes when UPS is on bypass.
6
TX
RMP II, RIM II, and SCM II connections.
7
TX
8
CAN L
9
Can H
CAN input for parallel operation.
10
Shield
INSTALLING OPTIONS AND ACCESSORIES
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status
Alarm
S
164201764 Rev 1 www.powerware.com