Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual page 30

1000–1100 kva
Table of Contents

Advertisement

UPS INSTALLATION PLAN AND UNPACKING
Table 3-5. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000, and 9395−1100/1100
– Separate Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Each Battery Disconnect to Each UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
A
B
C
NOTE Callout letters
,
,
, and
3−10
EATON Powerware
D
map to Figure 6-6 on page 6−8.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps per UPM
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
AWG or kcmil
(each)
S
164201764 Rev 1 www.powerware.com
Rating 50/60 Hz
1000
1100
909
1000
480/480
480/480
1280
1500
500
500
(5)
(5)
1203
1323
500
500
(4)
(5)
1203
1323
500
500
(5)
(6)
551
551
250
250
(3)
(3)
1203
1323
500
500
(4)
(5)
1203
1323
500
500
(5)
(6)
250
250
(1)
(1)