Figure 6-13. Typical Distributed Bypass System (1+1 And 2+0 Configurations) - Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual

1000–1100 kva
Table of Contents

Advertisement

UNDERSTANDING UPS OPERATION
A
– AC Input to UPS Rectifier
B
– AC Input to Bypass
C
– DC Input from Battery
D
– UPS AC Output to Tie Cabinet
E
– Output to Critical Load
*
– Overcurrent Protection provided by customer
*
NOTE This oneline does not show each UPM in the UPSs, but represents each UPS in the distributed bypass system. The internal
structure of each UPS is shown Figure 6-5 through Figure 6-8 starting on page 6−7.
NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral
conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.
6−18
EATON Powerware

Figure 6-13. Typical Distributed Bypass System (1+1 and 2+0 Configurations)

®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
A
B
*
*
E1
E6
UPS 2
E2
E7
Fuse
E3
E8
E12
CB1
(optional)
K1
CB4
Rectifier
Static
Switch
Fuse
K5
Fuse
Fuse
Inverter
K3
Battery
Converter
Fuse
K2
C
E4. E5
Battery Breaker
E9,
BATTERY SYSTEM
E10,
E11,
(Not supplied
E12
with the UPS)
D
S
164201764 Rev 1 www.powerware.com
A
B
*
*
E1
E6
UPS 1
E2
E7
Fuse
E3
E8
E12
CB1
(optional)
K1
CB4
Rectifier
Static
Switch
Fuse
K5
Fuse
Fuse
Inverter
K3
Battery
Converter
Fuse
K2
C
E4. E5
Battery Breaker
E9,
BATTERY SYSTEM
E10,
E11,
(Not supplied
E12
with the UPS)
D
TIE
CABINET
(Optional)
MOB 1
MOB 2
E
AC Output to
Critical Load