INSTALLING OPTIONS AND ACCESSORIES
UPS Can Card J3
Twisted Pair

Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring

5−10
EATON Powerware
Terminal TB1
Signal Connections
from the UPS

Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations

RMP II, RIM II, or SCM II
Table 5-5. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
J3–6 (TX)
J3–7 (TX)
N/A
N/A
N/A
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
To
Tightening Torque
RMP II, RIM II, or SCM II
TB1–5 (RDX*)
TB1–4 (RDX)
TB3 Line
TB3 Neutral
Ground Terminal
2.7 (24) Maximum
S
164201764 Rev 1 www.powerware.com
Ground
Terminal
Terminal TB3
120 Vac Power
Ground Terminal
Neutral
120 Vac from
Critical Bus
Line
Remarks
Nm (lb in)
0.9 (8)
Use twisted pair
0.9 (8)
0.9 (8)
0.9 (8)

Advertisement