UPS INSTALLATION PLAN AND UNPACKING
Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Powerware 9395−1100/1000
Powerware 9395−1100/1100
Powerware 9395−1100/650
Powerware 9395−1100/750
Powerware 9395−1100/825
3−2
EATON Powerware
For Field Installed UPM (FI−UPM) weights and dimensions, refe to the Powerware
9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.8 on
page 1−7.
Table 3-1. UPS Cabinet Weights
Model
Powerware 9395−1100/1000
Powerware 9395−1100/1100
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3-2.
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
From Front of Cabinet
From Back of Cabinet
From Right Side of Cabinet 152.4 mm (6") working space
From Left Side of Cabinet
The basic environmental requirements for operation of the UPS are:
S
Ambient Temperature Range:
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
If battery systems are located in the same room as the UPS, the battery manufacturer's environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-3.
Input/Output
Rating
Voltage
1000 kVA
480/480
1100 kVA
480/480
650 kVA
480/480
750 kVA
480/480
825 kVA
480/480
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
Section
ISBM
UPM
ISBM
UPM
457.2 mm (18") minimum clearance for ventilation
914.4 mm (36") working space
None Required
None Required
0–40°C (32–104°F)
95%, noncondensing
C A U T I O N
Heat Rejection
Ventilation Required for Cooling Air Exhaust
BTU/hr  1000 (kg−cal/hr)
195 (49127)
215 (54040)
127 (31933)
146 (36845)
161 (40530)
S
164201764 Rev 1 www.powerware.com
Weight
kg (lb)
Shipping
Installed
1850 (4078)
1750 (3858)
1590 (3505)
1482 (3267)
1850 (4078)
1750 (3858)
1590 (3505)
1482 (3267)
Approximately 3020 liter/sec (6400 cfm)