Eaton Powerware 9395 UPS 10001100 kVA Installation And Operation Manual page 29

1000–1100 kva
Table of Contents

Advertisement

Table 3-4. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100
– Common Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
A
B
C
NOTE Callout letters
,
,
, and
EATON Powerware
For four UPM external wiring requirements, including the minimum AWG size of
external wiring, see Table 3-4 for installations using a common battery system or
Table 3-5 for installations using a separate battery system. Wire sizes listed are for
copper wiring only.
For three UPM external wiring requirements, including the minimum AWG size of
external wiring, see Table 3-6 for installations using a common battery system or
Table 3-7 for installations using a separate battery system. Wire sizes listed are for
copper wiring only. Because of the future upgradability to a fully rated 1100 kVA UPS
with the addition of the FI−UPM, the UPS wiring is specified only for 1100 kVA in
Table 3-6 and Table 3-7.
D
map to Figure 6-5 on page 6−7.
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
UPS INSTALLATION PLAN AND UNPACKING
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Total Amps
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
AWG or kcmil
(each)
S
164201764 Rev 1 www.powerware.com
Rating 50/60 Hz
1000
1100
909
1000
480/480
480/480
1280
1500
500
500
(5)
(5)
1203
1323
500
500
(4)
(5)
1203
1323
500
500
(5)
(6)
2000
2203
500
500
(8)
(9)
1203
1323
500
500
(4)
(5)
1203
1323
500
500
(5)
(6)
250
2500
(1)
(1)
3−9