CAN
NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Figure 5-3. Distributed Bypass System Can and Pull−Chain Simplified Interface Wiring
Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
NOTE External CAN connections between UPSs require shielded twisted pair wire.
Table 5-2. CAN Bridge Card Wiring Terminations
From
UPS 1 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
EATON Powerware
UPS 1
UPS 2
Shielded Twisted Pair
UPS 2
CAN Bridge Card J3

Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs

To
UPS 2 CAN Bridge Card
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
®
9395 UPS (1000–1100 kVA) Installation and Operation Manual
INSTALLING OPTIONS AND ACCESSORIES
UPS 3
UPS 4
(If Installed)
(If Installed)
Shielded Twisted Pair
UPS 3
CAN Bridge Card J3
(If Installed)
To
UPS 3 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)
S
164201764 Rev 1 www.powerware.com
Pull Chain
UPS 4
CAN Bridge Card J3
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3–8 (L)
J3–9 (H)
J3–10 (Shield)