9.3 Disconnecting the PC from the station

9.4 Loading data to the 'Station'

Building Technologies
Fire Safety
As the IP address is bound to the MAC address while there is a connection
between the PC and the ↑ 'Station' and as it remains in the cache even in the case
of a short break in the connection of ≤2 min., you must observe the following
instructions.
NOTICE
Incorrect disconnection of 'Station'
Establishing a connection to other 'Station' is not possible
Disconnect the PC from the 'Station' as described in the following instructions.
The connection between the PC and the 'Station' must be disconnected as follows:
1. Select 'Cerberus-Engineering-Tool' > 'Commissioning' in Disconnect.
2. Disconnect the cable connection between PC and 'Station'.
3. Wait ≥2 min. before you establish a connection to another 'Station'.
Data is loaded from Cerberus-Engineering-Tool to the 'Station' when the following
commands are performed.
'Initialize station'
'Download site'
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
The table below shows which data is overwritten in the 'Station'.
Command
'Initialize station'
1
'Download site'
Command is only performed for the 'Station' that is connected to the PC via LAN.
1
The configuration of selected 'Stations' or all 'Stations' in the ↑ 'Site' can be
2
overwritten as an option.
See also
1 Loading configuration from the PC to the station [➙ 80]
1 Initializing 'Station' [➙ 78]
Connectivity and communication with 'Station'
Disconnecting the PC from the station
Overwrites the
Sets the address
↑ BDV
of the 'Station'
Yes
Yes
Yes
No
9
Overwrites the
configuration
Yes
Yes
2
77 | 118
A6V10211100_f_en_--
2015-12-15

Advertisement

Table of Contents
loading

Table of Contents