Installation
6
Supply concept

6.2.1 Operation with battery backup

6.2.2 Operation without battery backup

44 | 118
Building Technologies
Fire Safety
The ↑ stations are normally operated with a power supply unit and batteries. The
power supply unit feeds the hardware with galvanically isolated system voltage,
simultaneously charging the batteries.
Together with the batteries, the power supply unit assumes the function of an
uninterruptible power supply unit. The batteries are permanently fed via a
monitored output. In case of a mains voltage failure, the batteries take over the
power supply of the control panel without interruption.
The hardware is optimally protected and operational interruptions can be largely
avoided.
This operation mode protects the hardware against the following:
Voltage loss and undervoltage
Mains overvoltage (in accordance with EN 54)
High-energy interfering impulses (in accordance with EN 54)
Station
Power supply
#MAINS
U
mains
1
#BATT
5
Figure 17: Block diagram, power supply with battery backup
1
Electrical isolation
2
Umains / USys converter
3
Uninterrupted changeover switch
4
Batteries
5
Monitoring functions:
#MAINS: Mains voltage monitoring
#BATT: Battery monitoring
#CONV: Monitoring the output voltage
The stations can be operated without batteries. This operation mode is used when
the stations are operated via a network with external buffering, or when battery
backup is omitted.
The battery monitoring function can be deactivated by means of the hardware or
Cerberus-Engineering-Tool.
2
#CONV
~/=
U
battery
U
Sys
3
4
A6V10211100_f_en_--
2015-12-15