Initialize 'Station'
NOTICE
Connection module (card cage) FCA2006-A1 defective or installed incorrectly
Control panels identified incorrectly, e.g. FC726 identified as FC724.
Check that the connection module (card cage) FCA2006-A1 is installed
correctly.
NOTICE
Faulty initialization for networked station
During initialization, the station must not be connected to the network or any other
station.
ϖ The PC is connected locally to the ↑ 'Station'.
1. Highlight the 'Station' you want to initialize.
2. Select the 'Commissioning' > 'Initialize station' menu item.
 The following window is opened:
3. Click on 'Start'.
 The 'Set the station to access level 3' window opens.
4. Press <MENU> on the 'Station' and enter a valid PIN.
5. Click on 'OK' in the 'Set access level' window.
 The 'Station' is initialized.
 The 'Station' is restarted.
 After a few minutes, the 'Buzzer' sounds twice.
6. Press <Acknowledge> on the ↑ Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
Connectivity and communication with 'Station'
9
Initializing 'Station'
79 | 118
A6V10211100_f_en_--
2015-12-15