Restarting The Detector Line - Siemens Cerberus PRO FC721 Technical Manual

Fire control panel
Table of Contents

Advertisement

Commissioning
10
Detailed commissioning steps
10.8.8.2 Switch on zone

10.8.9 Restarting the detector line

100 | 118
Building Technologies
Fire Safety
1. Select 'Topology' > ↑ 'Detection tree' > 'Area' > ↑ 'Section' > 'Zone' in the main
menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'On' command.
 The yellow 'ISOLATION' LED goes out.
 The 'Zone' is switched on.
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
If necessary, block the outputs temporarily [➙ 101] before switching off the
station or restarting the station/detector line.
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > ↑ 'Station' > 'Module' (line
card) > 'Line'.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Restart line' command.
 The ↑ detector line is restarted. The following messages are displayed:
'Line starting up'
'Device config.runs'
Start line test
Only test the line and line devices once the following messages have disappeared
from the PMI:
- 'Device config.runs'
- 'System startup completed'
A6V10211100_f_en_--
2015-12-15