Building Technologies
Fire Safety
The connection terminals for the C-NET are on the periphery board.
Figure 24: Position of C-NET connection terminal on the periphery board
●
Max. 126 C-NET devices are permitted on the C-NET connection (block of 4
terminals).
●
The C-NET devices can be distributed on the loop (max. 126 devices) or on
two stubs (max. 32 devices per stub).
Loop connection example
●
Max. 126 line devices
-
4
+
3
-
2
+
1
Figure 25: C-NET loop circuit
Alternatively, the connection of two stubs instead of one loop is possible
Stub connection example
●
Max. 32 line devices per stub
●
Total of max. 64 line devices per line connection (4 terminals)
-
4
+
3
-
2
+
1
Figure 26: C-NET stub circuit
X11
Installation
6
C-NET detector line
Cerberus
T M
C
Cerberus
T M
C
63 | 118
A6V10211100_f_en_--
2015-12-15