Installing An Rs232/Rs485 Module - Siemens Cerberus PRO FC721 Technical Manual

Fire control panel
Table of Contents

Advertisement

Mounting
5
Options

5.5.2 Installing an RS232/RS485 module

1
RS232 module in slot X14 or
34 | 118
Building Technologies
Fire Safety
This component is installed in exactly the same way as for the operating units
with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027.
No more than one single interface module (RS232 or RS485) can be installed in an
FC721.
The serial modules include:
RS232 module (isolated), FCA2001
RS485 module (isolated), FCA2002
These modules are mounted in the slots designed for them on the operating unit.
The mounting procedure of the two serial modules is the same for all modules.
Space and location
Figure 10: Installation location of the serial modules
1
2
RS485 module in slot X19
2
A6V10211100_f_en_--
2015-12-15