Switching On Test Mode; Switch On Normal Operation - Siemens Cerberus PRO FC721 Technical Manual

Fire control panel
Table of Contents

Advertisement

Commissioning
10
Detailed commissioning steps

10.8.17 Switching on test mode

10.8.18 Switch on normal operation

104 | 118
Building Technologies
Fire Safety
1. Select 'Topology' > ↑ 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
 The yellow 'DETECTOR TEST' LED lights up.
 The element is in test mode.
Element
Area
↑ Section
Zone
There is a shortened procedure for switching individual 'Zones' to ↑ normal
operation. The procedure is described in the following section: 'Switching 'Zone' to
normal operation'
Switching 'Area', 'Section' or 'Zone' to ↑ normal operation
1. Select 'Topology' > ↑ 'Detection tree' in the main menu.
2. Select the element you want to switch to normal operation: 'Area', 'Section' or
'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
 The element is switched to normal operation.
 The yellow 'DETECTOR TEST' LED goes out.
Element
Area
↑ Section
Zone
Commands under 'Execute commands'
You can also switch to ↑ normal operation at superordinate level for the
command in question. Test mode can also be exited in the 'Zone', 'Section' or
'Area', for example.
Command
'Non-MCP zones det.test'
'MCP zones det.test'
'Non-MCP zones det.test'
'MCP zones det.test'
'Detector test'
Command
'Non-MCP zones det.test END'
'MCP zones det.test END'
'Non-MCP zones det.test END'
'MCP zones det.test END'
'Detector test END'
A6V10211100_f_en_--