4.2.1 Defining controls
RT alarm (relay)
Alarm output (monitored)
RT fault (relay)
Alarm output (monitored)
Monitored horn lines
Monitored contact inputs
Non-monitored control
outputs/contact inputs
Building Technologies
Fire Safety
Connections for controls are available on the following components / control
panels:
●
Fire control panels FC721
●
Input module FDCI221
●
Input module FDCI222
●
Input/output module FDCIO222
●
Input/output module FDCIO222
●
Input/output module FDCIO223
●
Input/output module FDCIO224
●
Addressable alarm indicator FDCAI224
The table below shows the control outputs available for the different hardware
modules.
FC721
FDCI221
1
–
1
–
1
–
1
–
1
–
–
1
–
4 freely
configurable
I/Os
Table 1: Control outputs in the fire detection system
Notes
●
The outputs can be used for any controls. Any events, commands and signal
inputs can be linked as an OR, AND and NOT relation.
●
Controls can be configured system-wide. This means that the causes can
come from any point in the system.
●
The controls can be configured as activated or deactivated with a delay in a
range of 0...30 minutes.
●
The onboard inputs/outputs in the fire control panel may be configured as
inputs or outputs.
●
If an onboard input/output is configured as an input in the fire control panel, it is
activated by applying 0 V.
●
If an onboard input/output is configured as an output in the fire control panel, it
switches 0 V when active (open drain).
FDCI222
FDCIO221
–
–
–
–
–
–
–
–
–
1
4
1
–
–
Planning
Functions
FDCIO223
FDCIO222/
FDCIO224
–
–
–
–
–
–
–
–
2
–
–
4
–
4 outputs
21 | 118
A6V10211100_f_en_--
2015-12-15