Advertisement

4.2.1 Defining controls

RT alarm (relay)
Alarm output (monitored)
RT fault (relay)
Alarm output (monitored)
Monitored horn lines
Monitored contact inputs
Non-monitored control
outputs/contact inputs
Building Technologies
Fire Safety
Connections for controls are available on the following components / control
panels:
Fire control panels FC721
Input module FDCI221
Input module FDCI222
Input/output module FDCIO222
Input/output module FDCIO222
Input/output module FDCIO223
Input/output module FDCIO224
Addressable alarm indicator FDCAI224
The table below shows the control outputs available for the different hardware
modules.
FC721
FDCI221
1
1
1
1
1
1
4 freely
configurable
I/Os
Table 1: Control outputs in the fire detection system
Notes
The outputs can be used for any controls. Any events, commands and signal
inputs can be linked as an OR, AND and NOT relation.
Controls can be configured system-wide. This means that the causes can
come from any point in the system.
The controls can be configured as activated or deactivated with a delay in a
range of 0...30 minutes.
The onboard inputs/outputs in the fire control panel may be configured as
inputs or outputs.
If an onboard input/output is configured as an input in the fire control panel, it is
activated by applying 0 V.
If an onboard input/output is configured as an output in the fire control panel, it
switches 0 V when active (open drain).
FDCI222
FDCIO221
1
4
1
Planning
Functions
FDCIO223
FDCIO222/
FDCIO224
2
4
4 outputs
21 | 118