Advertisement

6.4.3.1 Relay for fault and alarm (RT activation)
X7
X7
NO
NO
NO
Building Technologies
Fire Safety
Allocation of connection terminals on periphery board (1-loop) of FC721. A cable
cross-section of 0.2 to 1.5 mm
Designation
Description
6
FAU_NC
Break contact fault (normally closed)
5
FAU_COM
Center tap fault (common)
4
FAU_NO
Make contact fault (normally open)
3
AL_NC
Break contact alarm (normally closed)
2
AL_COM
Center tap alarm (common)
1
AL_NO
Make contact alarm (normally open)
The relays can be used e.g. for unmonitored activation of external devices.
Fault relay (inverse operation)
The fault relay is activated when at least one station fault has been detected. This
relay is activated when the control panel is in idle mode (NC/C, inverse operation).
In the event of a fault message, the relay changes the switching condition (to NO,
C). Thanks to inverse operation, a fault message will still be sent in the event of the
station losing all power.
+ Ub (DC)

Alarm relay

The alarm relay is activated when at least one station alarm message has been
detected.
Example of connection with external signal transmitter, e.g. an optical normal
operation/alarm message display.
+ Ub (DC)
Power supply - mains voltage connection
can be connected to the terminals.
2
Connection to an external monitoring
input (example)
Connection of external control
voltage e.g. for an acoustic or optical
fault message (example)
+
Normal operation
Alarm
Installation
6
Potential-free
directional contact
Max. DC 24 V / 1 A
Potential-free
directional contact
Max. DC 24 V / 1 A
53 | 118
A6V10211100_f_en_--
2015-12-15