ϖ The ↑ 'Site' is opened in Cerberus-Engineering-Tool.
ϖ The PC is connected to the 'Station'.
ϖ Networked 'Stations' are initialized.
ϖ 'Station' and Cerberus-Engineering-Tool have the same 'Site' ID.
ϖ 'Station' and Cerberus-Engineering-Tool are part of the same sales channel.
1. Select 'Commissioning' > 'Download site' in Cerberus-Engineering-Tool.
 The 'Download site' and 'Connect' windows open in Cerberus-Engineering-
Tool.
2. Select the connection in the 'Connect' window and click on 'OK'.
 The 'Stations' are listed in the 'Download site' window.
3. Select the 'Stations' whose configuration you would like to load from Cerberus-
Engineering-Tool to the 'Stations' and click on 'Start'.
 The 'Set access level' window may open in Cerberus-Engineering-Tool with
the 'Set the station to access level 3' prompt. Press <MENU> on the
'Station', enter the PIN and press <ok>.
4. Click on 'OK' in the 'Set access level' window in Cerberus-Engineering-Tool.
 The 'Action confirmation' window opens in Cerberus-Engineering-Tool.
5. Click on 'Yes'.
 The configuration is loaded to the 'Station'.
 The progress is displayed in the 'Download site' window in Cerberus-
Engineering-Tool.
 The 'Station' restarts.
 After a few minutes, the 'Buzzer' sounds twice at the 'Station'.
6. Press <Acknowledge> on the ↑ Person Machine Interface at the 'Station' to
switch off the 'Buzzer'. Do not perform any more actions on the 'Station' until
the 'Buzzer' has sounded for the second time.