Wiring Principle Behind C-Net Devices - Siemens Cerberus PRO FC721 Technical Manual

Fire control panel
Table of Contents

Advertisement

Installation
6
C-NET detector line

6.5.3 Wiring principle behind C-NET devices

Wiring example of C-NET detector devices on loop
64 | 118
Building Technologies
Fire Safety
Cable types
As a result of national standards and requirements, installation may require a
particular cable type. Note the respective requirements and planning documents.
The following cable types can always be used for cabling the detector line:
Twisted, with and without shielding (recommended)
Untwisted, with and without shielding
Cable shielding
When using shielded lines (e.g. fire detection cable J-Y(St)Y n x 2 x 0.8 mm),
ensure that the cable shielding is only connected on one side.
The fire control panel's function may be impaired by a missing or incorrect cable
shielding connection. The 'Shield connection terminal blocks' option is available for
the connection. Depending on the installation environment and requirements of
relevant standards, cable shielding may have to be connected and merged at one
central connection point.
The screw terminals for directly connecting the C-NET cable are integrated in every
C-NET line device. The connection terminals with input (+/-) and output (+/-) are
the same for all users, with the exception of the detector base.
Connection terminal
Detector base and sounder
base
1b (corresponds to +,
input/output)
5 (corresponds to input)
6 (corresponds to output)
Manual call point
Input/output modules
Transponder
Alarm sounder with beacon
A6V10211100_f_en_--
2015-12-15

Advertisement

Table of Contents
loading

Table of Contents