Siemens Cerberus PRO FC721 Technical Manual page 55

Fire control panel
Table of Contents

Advertisement

6.4.3.3 Connection of monitored acoustic signal transmitters
X6
X6
Building Technologies
Fire Safety
Connection terminals on the periphery board (1-loop) of FC721. A cable cross-
section of 0.2 to 1.5 mm
Designation
Description
6
FAU_OUT
Output fault
5
VSYS_O
Supply output for consumer fault
4
AL_OUT-
Alarm output (-)
3
AL_OUT+
Alarm output (+)
2
SOUND1-
Output for acoustic signal transmitter (-)
1
SOUND1+
Output for acoustic signal transmitter (+)
Diagram showing principle
In normal operation, the connection is monitored for wire breaks and short-circuits
on the connection line. A monitoring current flows through the termination resistor
R (2.3 kOhm to 5.5 kOhm). All resistance values outside this range are recognized
as faults. The termination resistor should be connected directly to the connection
terminals of the monitored signal transmitter.
In the event of an alarm (with output activated), the polarity on the connection
terminal is reversed and the blocking diode is switched in the conducting direction.
The external signal transmitter is activated with the output voltage (+DC 24 V).
+
Fx ⇒ SMD fuse 1 A/T (on the periphery board)
R ⇒ terminating resistor (coverage area 2.3 kohms – 5.5 kohms)
V ⇒ blocking diode type 1N 4xxxx
M ⇒ flow of current in normal operation (monitoring)
A ⇒ flow of current during an alarm
Note total current of the station (e.g. max. 2.5 A for the 70 W power unit).
Power supply - mains voltage connection
can be connected to the terminals.
2
M
Installation
6
Potential-free
directional contact
Max. DC 24 V / 1 A
+
+
55 | 118
A6V10211100_f_en_--
2015-12-15