6.2

Downloading new operator panel firmware from the PC

Description
Firmware might need to be loaded to the AOP if the AOP functionality needs to be upgraded.
If, once the drive has powered up, the memory card is found to contain a newer version of
the firmware, a message will appear on the AOP30 prompting you to load the new firmware.
You should click "YES" in response to this prompt.
The firmware will then be loaded automatically on the operator panel and the following dialog
screen will appear.
Figure 6-2
If the firmware cannot be loaded successfully, it can be loaded using the following manual
method.
The load program LOAD_AOP30 and the firmware file can be found on the CD.
Loading the firmware
1. Establish the RS232 connection from the PC to the AOP30.
2. Provide the supply voltage (24 VDC).
3. Start the LOAD_AOP30 program on the PC.
4. Choose the PC interface (COM1, COM2).
5. Choose and open the firmware (AOP30.H86).
6. Follow the instructions in the status window of the program and connect the power supply
for the AOP30 while pressing the red key (O).
7. The load procedure is started automatically.
8. Switch the power on (switch the power supply off and then back on).
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
6.2 Downloading new operator panel firmware from the PC
Dialog screen: loading firmware
Maintenance and servicing
51