Loading Configuration From The Pc To The Station - Siemens Cerberus PRO FC721 Technical Manual

Fire control panel
Table of Contents

Advertisement

Connectivity and communication with 'Station'
9

Loading configuration from the PC to the station

9.6 Loading configuration from the PC to the station
80 | 118
Building Technologies
Fire Safety
You can use the 'Download site' function to load the configuration of one ↑ 'Site'
from the Cerberus-Engineering-Tool on the PC into the 'Station'.
NOTICE
Different network configuration in Cerberus-Engineering-Tool and networked
↑ 'Site'
When the selection displayed for 'Download site' is manually modified, in special
cases
it may be necessary to reset a 'Station' to the factory setting as well as a
1
'Initialize station'.
Do not modify the selection displayed for 'Download site' in normal cases.
Check the sequence when loading different configuration states in special
cases
.
1
After any change of the network configuration, make sure that all 'Stations' in
the 'Site' for the 'Download site' procedure are selected and can be accessed.
Temporarily update non-accessible 'Stations' to the latest status of the global
network configuration prior to integration in the network.
Examples of special cases:
1
A 'Station' will be added to a networked ↑ 'Site' and a new network
configuration will be loaded upon initialization of this 'Station', different from the
global network configuration of the connected 'Site'.
During the 'Download site' procedure a 'Station' is temporarily not accessible.
Both examples can result in the 'Station' no longer starting after the 'Download site'
procedure and the above actions having to be carried out.
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
If necessary, block the outputs temporarily [➙ 101] before switching off the
station or restarting the station/detector line.
A6V10211100_f_en_--