CHAPTER 10: DIGITAL FAULT RECORDER

Transient recorder settings

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Select the Settings > DFR > Transient Record menu item to open the transient recorder
function configuration window.
Figure 444: Transient recorder function settings
The following settings are available.
Function
Range: Enabled, Disabled
Default: Enabled
This setting enables and disables the transient recorder function.
Number Of Records
Range: 1 to 64 in steps of 1
Default: 48
This setting specifies the total number of transient records that can be stored in the
Plus
D90
. A larger setting results in a shorter record length, and vice-versa.
Trigger Mode
Range: Automatic Overwrite, Protected
Default: Automatic Overwrite
If this setting is selected as "Automatic Overwrite", then the oldest record will be
overwritten once the number of stored records reaches the setting value. If this setting is
"Protected", then no new records are stored once the number of records reaches the
setting value.
Trigger Position
Range: 1 to 100% in steps of 1
Default: 50%
This setting specifies the amount of pre-trigger data stored in a record expressed as a
percentage of record length.
Maximum Re-Triggers
Range: 1 to 4 in steps of 1
Default: 2
This setting selects the maximum number of re-trigger records that can be generated
for an event. The value is limited to one less than the number of records that can be
stored (up to a maximum of four records).
TRANSIENT RECORDER
515