CHAPTER 10: DIGITAL FAULT RECORDER
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Available Signals
Range: any FlexAnalog™ quantity
Default: Off
This setting specifies the FlexAnalog™ quantity to be recorded for the channel. The size
of each disturbance record depends in part on the number of parameters selected.
Parameters set to "Off" are ignored.
High Triggering
Range: Off, Trigger Only, Trigger/Re-Trigger, Re-Trigger Only
Default: Off
This setting selects the high triggering function for the analog channel. When set to
"Trigger Only" or "Trigger/Re-Trigger", the disturbance recorder will initiate data capture
when the magnitude of the signal is greater than the value of the
The resulting record will contain pre-fault and fault data. The channel must return to the
OFF state before it can generate a subsequent trigger.
When set to "Re-Trigger Only" or "Trigger/Re-Trigger", the disturbance recorder will be
re-triggered when the magnitude of the signal is greater than the value of the
Pickup
setting. The resulting record will contain fault data only. A re-trigger is again
generated at the end of a disturbance record if the magnitude is greater than the
and if the number of re-triggers is less than the
Pickup
Note that only phasor magnitudes, RMS magnitudes, frequency, and power may be used
as analog triggers.
High Pickup
Range: 0.0 to 1000000.0 in steps of 0.1
Default: 1000.0
This setting specifies the magnitude of the signal required to produce a trigger or re-
trigger. This setting is expressed in primary values. The units are dependent on the value
of the
Available Signal
setting.
Low Triggering
Range: Off, Trigger Only, Trigger/Re-Trigger, Re-Trigger Only
Default: Off
This setting selects the low triggering function for the analog channel. When set to
"Trigger Only" or "Trigger/Re-Trigger", the disturbance recorder will initiate data capture
when the magnitude of the signal is less than the value of the
resulting record will contain both pre-fault and fault data. The channel must return to the
off state before it can generate a subsequent trigger.
When set to "Trigger/Re-Trigger" or "Trigger Only", the disturbance recorder will be re-
triggered when the magnitude of the signal is less than the value of the
setting. The resulting disturbance record will contain fault data only. A re-trigger is
generated again at the end of the record if the magnitude is less than the
and if the number of re-triggers is less than the
Note that only phasor magnitudes, RMS magnitudes, frequency, and power may be used
as analog triggers.
Low Pickup
Range: 0.0 to 1000000.0 in steps of 0.1
Default: 1000.0
This setting specifies the magnitude of the signal required to produce a trigger or re-
trigger. This setting is expressed in primary values. The units are dependent on the value
of the
setting.
Available Signal
DISTURBANCE RECORDER
High Pickup
Maximum Re-Trigger
setting. The
Low Pickup
Low Pickup
setting.
Maximum Re-Trigger
setting.
High
High
setting.
Low Pickup
527