GE D90 Plus Instruction Manual page 396

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

PROTECTION INPUTS AND OUTPUTS
NOTE:
CAUTION:
Contact input and output default assignment
386
The FlexLogic™ operand response time to the contact input change is equal to the
debounce time setting plus a maximum of one protection pass (depending on system
frequency if frequency tracking is enabled). If the change of state occurs just after a
protection pass, the recognition is delayed until the subsequent protection pass (that is, by
the entire duration of the protection pass). If the change occurs just prior to a protection
pass, the state is recognized immediately. Statistically, a delay of half the protection pass is
expected. Owing to the 0.25 ms scan rate, the time resolution for the input contact is less
than 1 ms.
For example, sixteen protection passes per cycle on a 60 Hz system correspond to a
protection pass every 1.04 ms. With a contact debounce time setting of 3.0 ms, the
FlexLogic™ operand assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 1.04 = 4.04 ms.
These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped
with a 1 ms accuracy using the time of the first scan corresponding to the new state.
Therefore, the time stamp reflects a change in the DC voltage across the contact input
terminals that was not accidental as it was subsequently validated using the debounce
timer. Keep in mind that the associated FlexLogic™ operand is asserted/de-asserted later,
after validating the change. The debounce algorithm is symmetrical: the same procedure
and debounce time are used to filter the OFF-ON and ON-OFF transitions.
The active impedance feature controls the input impedance presented to the system
according to the current state of the input. When the contact input circuitry initially detects
a voltage increase, it will draw 10 mA of current. If the state change is due to a transient
coupled through the stray capacitance of the field wiring, then the high current sink will
charge the capacitance causing the transient to rapidly decay. If voltage increase is due to
a state change of the field contact, then the increased current will have no impact on the
input voltage, and the state change will be validated. Once the input has been declared to
be on, the input circuitry will reduce the current drawn to 1 mA to minimize the power
dissipated by the input.
The contact input update time is 1 ms. However, depending on where the contact input
status change is triggered within a one millisecond window, the worst-case contact input
recognition time will be 2 ms.
Plus
If a D90
unit with firmware revision 1.60 is changed to firmware 1.50 or lower, then
the contact input and output calibration values will be lost.
When a new settings file is created, the available contacts are automatically assigned to
the protection or automation functions according to the following convention.
First I/O module → protection.
All subsequent I/O modules → automation.
Plus
For example, if a D90
is configured with contact input/output cards in slots E, F, and G,
then the inputs and outputs associated with slot E are assigned to protection and the
inputs and outputs associated with slots F and G are assigned to automation.
These default assignments may be changed to match the requirements of the application.
This is done by right-clicking on the setting filename and choosing the menu Manage
Settings File > I/O Assignments menu item. The following window is displayed.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: PROTECTION

Advertisement

Table of Contents
loading

Table of Contents