GE D90 Plus Instruction Manual page 89

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 5: ENERVISTA SOFTWARE SUITE
Editing a settings template
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
The settings template editing feature allows the user to specify which settings are
available for viewing and modification in EnerVista UR
except the FlexLogic™ equation editor settings are locked.
1.
Select an installed device or a settings file from the tree menu on the left of the
Plus
EnerVista UR
Setup main screen.
2.
Select the Template Mode > Edit Template option (online mode) or the Settings File
Template > Edit Template option (offline mode) to place the device or settings file in
template editing mode.
3.
Enter the template password (if required) then click OK.
4.
Open the relevant settings windows that contain settings to be specified as viewable.
By default, all settings are specified as locked and displayed against a grey
background. The icon on the upper right of the settings window will also indicate that
Plus
EnerVista UR
Setup is in edit mode. The following example shows the phase time
overcurrent settings window in edit mode.
5.
Specify which settings to make viewable by clicking on them.
The settings selected as available to view will be displayed against a yellow
background as shown below.
6.
Click on Save to save changes to the settings template.
Only the settings that are available for editing are saved to the device or setting file.
Plus
EXTENDED ENERVISTA UR
Plus
Setup. By default, all settings
SETUP FEATURES
79

Advertisement

Table of Contents
loading

Table of Contents