CHAPTER 7: PROTECTION
Neutral overvoltage
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 227: Phase overvoltage scheme logic
There are three neutral overvoltage elements available. The neutral overvoltage element
can be used to detect asymmetrical system voltage condition due to a ground fault or to
the loss of one or two phases of the source. The element responds to the system neutral
voltage (3V_0), calculated from the phase voltages. The nominal secondary voltage of the
phase voltage channels entered in the
used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic
versus the applied voltage (initialized from FlexCurves™ A, B, or C) or be used as a definite
time element. The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element.
This function requires the VTs to be wye-connected.
Select the Settings > Protection > Elements > Group 1 > Voltage > Neutral OV menu item
to open the neutral overvoltage configuration window.
Figure 228: Neutral overvoltage configuration settings
The following settings are available for each neutral overvoltage element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the neutral overvoltage protection element.
GROUPED PROTECTION ELEMENTS
setting is the per-unit base
Phase VT Secondary
267