ELECTRICAL INSTALLATION
62
Figure 31: Link LEDs for fiber, RS422, and G.703 modules
The following table describes the operation of the link LEDs.
Table 4: Link LED operation
Protocol LED indications
Red, solid
Green, solid
IEEE
Loss of
Signal detected,
C37.94
signal
but not receiving
valid data
Direct
Loss of
Signal detected,
fiber
signal
but not receiving
valid data
G.703
Loss of
Signal detected,
signal
but not receiving
valid data
RS422
Loss of
Clock detected,
clock
but not receiving
valid data
Green, blinking
Signal detected
and receiving valid
data; yellow bit
alarm not set
Signal detected
and receiving valid
data
Signal detected
and receiving valid
data
Clock detected
and receiving valid
data
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Yellow, blinking
Signal detected, receiving valid
data and the received yellow bit
alarm is set; the yellow bit indicates
that remote unit is not receiving
valid data
Not used
Not used
Not used