GE D90 Plus Instruction Manual page 243

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Select the Settings > Protection > Elements > Group 1 > Current > Phase TOC menu item
to open the phase time overcurrent configuration window.
Figure 198: Phase time overcurrent configuration settings
The following settings are available for each phase time overcurrent element.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phase time overcurrent protection element.
Signal Source
Range: LINE (SRC 1), BKR 1 (SRC 2), BKR 2 (SRC 3)
Default: LINE (SRC 1)
This setting selects the signal source for the phase time overcurrent protection element.
Input
Range: Phasor, RMS
Default: Phasor
This setting selects how phase current input quantities are interpreted by the D90
Inputs can be selected as fundamental phasor magnitudes or total waveform RMS
magnitudes as required by the application.
Pickup
Range: 0.000 to 30.000 pu in steps of 0.001
Default: 1.000 pu
This setting specifies the phase time overcurrent pickup level in per-unit values.
Curve
Range: IEEE Mod Inv, IEEE Very Inv, IEEE Ext Inv, IEC Curve A, IEC Curve B, IEC Curve C, IEC
Short Inv, IAC Ext Inv, IAC Very Inv, IAC Inverse, IAC Short Inv, I2t, Definite Time, FlexCurve A,
FlexCurve B, FlexCurve C, FlexCurve D
Default: IEEE Mod Inv
This setting selects the time inverse overcurrent curve style.
TD Multiplier
Range: 0.00 to 600.00 in steps of 0.01
Default: 1.00
This setting specifies a multiple of the base curve shape specified by the
Programming this value to zero results in an instantaneous response to all current levels
above pickup.
GROUPED PROTECTION ELEMENTS
Plus
setting.
Curve
.
233

Advertisement

Table of Contents
loading

Table of Contents