Advertisement

CHAPTER 6: COMMUNICATIONS

IEC 61850 server configuration

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Table 8: Per-unit base units
Element
Frequency
Phase angles
Power factor
Source current
Source power
Source voltage
The GOOSE analog input FlexAnalog™ values are available for use in other
Plus
D90
functions that use FlexAnalog™ values.
Select the Settings > Communications > IEC 61850 > Server Configuration menu item to
open the IEC 61850 server configuration window.
Figure 100: IEC 61850 server configuration settings
The following settings are available.
IED Name
Range: up to 32 alphanumeric characters
Default: IEDName
This setting represents the MMS domain name where all IEC/MMS logical nodes are
located. Changes to this setting and the GOOSE dataset will not take effect until the unit
is restarted. The setting value can be composed of up to 32 characters, including upper
and lowercase letters, numbers, and the underscore (_) character. The first character in
the string must be a letter.
Logical Device Instance
Range: up to 32 alphanumeric characters
Default: LDInst
This setting represents the IEC 61850 logical device where all IEC/MMS logical nodes are
located. The setting value can be composed of up to 32 characters, including upper and
lowercase letters, numbers, and the underscore (_) character. The first character in the
string must be a letter.
LPHD DC PhyNam Location
Range: up to 80 ASCII characters
Default: Location
This setting represents a string that appears within the PhyName of the LPHD node. It
can be composed of up to 80 characters, including upper and lowercase letters,
numbers, and the underscore (_) character. The first character in the string must be a
letter.
Base unit
1 Hz
360 degrees
1.00
Maximum nominal primary RMS value of the +IN and –IN inputs
Maximum value of the product of the voltage and current base
values for the +IN and –IN inputs.
Maximum nominal primary RMS value of the +IN and –IN inputs.
IEC 61850 COMMUNICATIONS