PHASOR MEASUREMENT UNIT

Phasor measurement unit reporting over network

552
The phasor measurement unit Ethernet connection works simultaneously with other
communication means over Ethernet. The network reporting feature is programmed via
the Settings > Metering > Phasor Measurement Unit > Reporting Over Network menu.
Figure 481: Phasor measurement unit reporting over network configuration settings
The following settings are available for each phasor measurement unit.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the phasor measurement unit reporting over network
feature.
ID Code
Range: 1 to 65534 in steps of 1
Default: 1
This setting specifies an IDCODE for the entire port. Individual phasor measurement unit
streams transmitted over this port are identified via their own IDCODEs as per the
phasor measurement unit IDCODE settings. This IDCODE is to be used by the command
frame to start and stop transmission, and request configuration or header frames.
Rate
Range: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times per second
Default: 10 times per second
This setting specifies the reporting rate for the network (Ethernet) port. This value applies
to all phasor measurement unit streams of the device that are assigned to transmit over
this port.
Style
Range: Polar, Rectangular
Default: Polar
This setting selects between reporting synchrophasors in rectangular (real and
imaginary) or in polar (magnitude and angle) coordinates. This setting complies with bit-
0 of the format field of the C37.118 configuration frame.
Format
Range: Integer, Floating
Default: Integer
This setting selects between reporting synchrophasors as 16-bit integer or 32-bit IEEE
floating point numbers. This setting complies with bit 1 of the format field of the C37.118
configuration frame. Note that this setting applies to synchrophasors only – the user-
selectable FlexAnalog™ channels are always transmitted as 32-bit floating point
numbers.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL