CHAPTER 7: PROTECTION
2
I
t curves
FlexCurves™
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
2
The I
t curves are derived as follows.
The terms in the above equations are defined as follows.
T
represents the operate time in seconds.
operate
TDM represents the multiplier setting.
I represents the input current.
I
represents the pickup current setting value.
pickup
T
represents reset time in seconds, assuming the energy capacity is 100% and the
reset
reset mode is timed.
2
Table 12: I
t curve trip times (in seconds)
Multiplier
Current (I / I
pickup
(TDM)
1.5
2.0
0.01
0.44
0.25
0.10
4.44
2.50
1.00
44.44
25.00
10.00
444.44 250.00 111.11 62.50
100.00
4444.4 2500.0 1111.1 625.00 400.00 277.78 204.08 156.25 123.46 100.00
600.00
26666.
15000.
7
0
The custom FlexCurve™ shapes are defined as follows.
The terms in the above equations are defined as follows.
T
represents the operate time in seconds.
operate
TDM represents the multiplier setting.
I represents the input current.
I
represents the pickup current setting value.
pickup
T
represents reset time in seconds, assuming the energy capacity is 100% and the
reset
reset mode is timed.
)
3.0
4.0
5.0
6.0
0.11
0.06
0.04
0.03
1.11
0.63
0.40
0.28
11.11
6.25
4.00
2.78
40.00
27.78
6666.7 3750.0 2400.0 1666.7 1224.5 937.50 740.74 600.00
GROUPED PROTECTION ELEMENTS
7.0
8.0
9.0
10.0
0.02
0.02
0.01
0.01
0.20
0.16
0.12
0.10
2.04
1.56
1.23
1.00
20.41
15.63
12.35
10.00
Eq. 16
Eq. 17
Eq. 18
Eq. 19
231