CHAPTER 7: PROTECTION
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
must be greater than the
Current Cutoff Level
Power System > AC Inputs – Current menu. The following figure explains the usage of the
voltage polarized directional unit of the element.
Figure 220: Negative-sequence directional characteristics
The forward-looking function is designed to be more secure as compared to the reverse-
looking function, and therefore, should be used for the tripping direction. The reverse-
looking function is designed to be faster as compared to the forward-looking function and
should be used for the blocking direction. This allows for better protection coordination.
The above bias should be taken into account when using the negative-sequence
directional overcurrent element to directionalize other protection elements.
Select the Settings > Protection > Elements > Group 1 > Current > Negative Sequence
Directional OC menu item to open the negative-sequence directional overcurrent
configuration window.
GROUPED PROTECTION ELEMENTS
setting value specified in the Protection >
259